UL

24V Logic Power Supply Fault

Phoenix Contact · AXC F 1050 Controller

Hva betyr UL ?

This indicator, when off, shows that the 24V communications power feed-in for the logic section (ULogic) is either completely absent or its voltage level is too low. This critical condition prevents the Axioline F station from operating correctly.

Vanlige årsaker

  • Absence of 24VDC communications power supply.
  • 24VDC communications power supply voltage is below the operational threshold.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the 24VDC power supply voltage at the communications power feed-in terminals of the Axioline F station.

  2. 2

    Verify the power supply unit providing the 24VDC for correct output voltage and current capacity.

  3. 3

    Inspect the power cabling from the 24VDC supply to the Axioline F station for breaks or loose connections.