Too Hot

Refrigeration Too Hot

Otis · 400 Elevator

Hva betyr Too Hot ?

Indicates that the refrigeration temperature is 1.5º C above the compressor cut-in setting, suggesting the unit is not cooling sufficiently. This can compromise product integrity and safety.

Vanlige årsaker

  • Refrigeration system failure to cool effectively.
  • High ambient temperature affecting cooling performance.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the accuracy of the refrigeration temperature sensor against a calibrated reference thermometer.

  2. 2

    Measure the supply voltage at the compressor input terminals and verify compressor operation (audible running, vibration).

  3. 3

    Inspect condenser and evaporator coils for cleanliness, obstructions, and verify proper airflow from fans.

  4. 4

    Check the refrigeration unit's control parameters, specifically the compressor cut-in/cut-out temperature setpoints, against documentation.