54015600 hex

Illegal CNC Coordinate System Specification

Omron · NJ/NX-series Machine Automation Controller

Hva betyr 54015600 hex ?

The CNC coordinate system specified for the Coord in-out variable in a CNC instruction does not exist. This indicates a programming or configuration error where a non-existent coordinate system is referenced.

Vanlige årsaker

  • CNC coordinate system does not exist for the variable specified for the Coord in-out variable to the instruction.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect the CNC program (e.g., G-code, Function Block parameters) to locate the instruction referencing the `Coord` in-out variable and identify the specified coordinate system name/ID.

  2. 2

    Check the Omron NJ/NX controller's motion control settings and axis group configurations to verify the definition and existence of all configured CNC coordinate systems.

  3. 3

    Compare the coordinate system name/ID identified in the CNC program with the configured coordinate systems in the controller to confirm an exact match and proper declaration.