Oversetter...
095

Free Setting V/f Frequency 7 Exceeds Multi-step Speed Reference 0

Omron · MX2 Inverter

Hva betyr 095 ?

This warning occurs when the seventh point of the free setting V/f curve (b112) is set higher than Multi-step speed reference 0 (A020) or the output frequency setting (F001). This creates a conflict where the V/f curve's maximum frequency is inconsistent with a programmed speed reference, potentially causing unintended speed limits.

Vanlige årsaker

  • Parameter b112 (Free setting V/f curve frequency point 7) is configured to a value higher than the Multi-step speed reference 0 (A020).
  • The V/f curve's maximum frequency defined by b112 is set above the nominal operating frequency for multi-step speed reference 0 (A020).
  • The current output frequency setting (F001) is lower than b112, indicating a discrepancy between the V/f curve maximum and the active frequency command.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Read the current values of parameter b112, A020 (Multi-step speed reference 0), and F001 (Output frequency setting) from the drive.

  2. 2

    Adjust parameter b112 to be less than or equal to the desired Multi-step speed reference 0 (A020).

  3. 3

    Verify that the output frequency setting (F001) is consistent with the desired A020 and b112 values, adjusting external commands if necessary.

  4. 4

    Save the modified parameters to the drive's non-volatile memory and power cycle the drive.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder