Oversetter...
091

Free Setting V/f Frequency 7 Exceeds Upper Limit

Omron · MX2 Inverter

Hva betyr 091 ?

This warning occurs when the seventh point of the free setting V/f curve (b112), which also acts as the maximum frequency in this mode, is set higher than the frequency upper limit (A061). This creates an inconsistent operational boundary for V/f control, limiting the actual achievable frequency.

Vanlige årsaker

  • Parameter b112 (Free setting V/f curve frequency point 7) is configured with a value exceeding parameter A061 (Frequency upper limit).
  • An incorrect V/f curve profile was entered during setup, causing b112 to inadvertently exceed the system's global frequency upper limit A061.
  • During system commissioning, parameter A061 was set to a value lower than the intended operating maximum frequency defined by b112.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Read the current value of parameter b112 (Free setting V/f curve frequency point 7) and parameter A061 (Frequency upper limit) from the drive's display or programming software.

  2. 2

    Adjust parameter b112 to be less than or equal to the desired A061, ensuring the V/f curve point respects the frequency upper limit.

  3. 3

    Alternatively, if a higher maximum operational frequency is required, increase parameter A061 to a value greater than or equal to b112, within motor and application limits.

  4. 4

    Save the new parameter settings to non-volatile memory and cycle power to the inverter to apply changes.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder