Oversetter...
025

Lower Limit Exceeds Multi-step Speed Reference 0

Omron · MX2 Inverter

Hva betyr 025 ?

This warning indicates that the frequency lower limit (A062) is set higher than the Multi-step speed reference 0 (A020) or the output frequency setting (F001). This creates a logical inconsistency where the minimum allowed frequency is greater than a programmed speed reference, potentially limiting operation.

Vanlige årsaker

  • A062 (Frequency Lower Limit) was manually configured to a value exceeding A020 (Multi-step Speed Ref 0).
  • A020 (Multi-step Speed Ref 0) was inadvertently lowered to a value below the configured A062.
  • An external frequency command (driving F001) is scaled incorrectly or experiencing noise, causing it to momentarily fall below A062 while A020 is active.
  • A logical inconsistency introduced during parameter setup, where the minimum operating frequency is set above a specific speed reference.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Access parameters A062 (Frequency Lower Limit) and A020 (Multi-step Speed Reference 0). Compare their values.

  2. 2

    Adjust A062 (Frequency Lower Limit) to be less than or equal to A020 (Multi-step Speed Reference 0).

  3. 3

    Alternatively, if the application requires A020 to be higher, increase A020 (Multi-step Speed Reference 0) to be equal to or greater than A062.

  4. 4

    If F001 (Output Frequency) is causing the issue when A020 is active, monitor the actual output frequency and verify consistency with A020.

  5. 5

    Save the parameter changes and power cycle the drive to confirm the settings are active.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder