A295.11

No END Error

Omron · CJ-series CJ2 CPU Unit

Hva betyr A295.11 ?

The program is missing an END(001) instruction at the conclusion of the task specified in A294. This indicates an incomplete program structure, preventing proper task execution and leading to a fatal program error (0x80F0).

Vanlige årsaker

  • An END(001) instruction is not present at the end of the task identified in A294 (program stop task number).

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Locate the task number specified in A294.

  2. 2

    Verify the presence of an END(001) instruction at the end of that task.

  3. 3

    Insert the END(001) instruction if missing.