0x80EA

Expansion Rack Starting Word Address Exceeded

Omron · CJ-series CJ2 CPU Unit

Hva betyr 0x80EA ?

An Expansion Rack's starting word address exceeds CIO 0901, preventing the CPU from correctly addressing the I/O for the rack. The corresponding bit in A409.00 to A409.03 (Racks 0 to 3) will be turned ON, indicating the affected rack.

Vanlige årsaker

  • The first word setting for the Expansion Rack is configured above CIO 0900.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the first word setting for the Rack indicated by A409.00 to A409.03.

  2. 2

    Using a Programming Device (e.g., CX-Programmer), change the setting to a valid word address below CIO 0900.

Se alle koder i denne manualen (34)
Verifisert teknisk data. Sist oppdatert: March 2026