0x80E9
Unit/Rack Number Duplication Error
Omron · CJ-series CJ2 CPU Unit
Hva betyr 0x80E9 ?
The same number has been allocated to more than one CPU Bus Unit or Special I/O Unit. This is a fatal error, indicated by flag A401.13. Auxiliary Area A410 and A411 to A416 will indicate the duplicated unit numbers for CPU Bus Units and Special I/O Units respectively.
Vanlige årsaker
- The same unit number has been assigned to multiple CPU Bus Units.
- The same unit number has been assigned to multiple Special I/O Units.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the unit numbers configured for all CPU Bus Units and Special I/O Units.
- 2
Eliminate any duplicate unit number assignments in the configuration.
- 3
Cycle the Rack's power supply OFF and then ON again after correcting the unit numbers.
Verifisert teknisk data. Sist oppdatert: March 2026