Oversetter...
5-time blink 2.5-second OFF

Outdoor Power System / Compressor Protection

Mitsubishi Electric · Mitsubishi MSZ-FH06-18NA Heat Pump System

Hva betyr 5-time blink 2.5-second OFF ?

This fault is triggered when the compressor stops three consecutive times within one minute of startup due to overcurrent protection or startup failure protection. It points to significant issues within the outdoor unit's power delivery, compressor, or refrigeration system. Leaving this unresolved risks severe damage to the compressor and other critical components.

Vanlige årsaker

  • Locked rotor condition or excessive mechanical load on the compressor, causing high inrush current beyond the inverter's capacity.
  • Low refrigerant charge or a restriction in the refrigeration system (e.g., clogged filter drier, kinked line) leading to abnormal operating pressures and increased compressor workload.
  • Imbalance or phase loss in the three-phase power supply (e.g., L1, L2, L3) to the outdoor unit, causing uneven current draw and motor stress.
  • Faulty compressor motor windings (e.g., short to ground, inter-turn short) resulting in excessive current draw during startup attempts.
  • Inverter P.C. board fault, specifically in the IGBT power module or current sensing circuit, causing erroneous overcurrent detection or failure to drive the compressor correctly.
  • Loose or corroded power terminals (e.g., U, V, W to compressor, L1, L2, L3 input) leading to high resistance and voltage drop under load.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Disconnect main power to the outdoor unit. Using an insulation resistance tester (Megger), measure the insulation resistance of the compressor motor windings to ground and between phases (U-V, V-W, W-U).

  2. 2

    Check the refrigerant charge pressure (e.g., high-side and low-side) using a manifold gauge set. Verify pressures are within the manufacturer's specified operating range for the ambient temperature.

  3. 3

    Verify input line voltage (L1-L2, L2-L3, L3-L1) and phase balance using a multimeter at the main power terminals (e.g., TB1) during startup attempt (briefly).

  4. 4

    Inspect all compressor power wiring (U, V, W terminals) for tightness, corrosion, or signs of overheating. Ensure proper torque on terminal connections.

  5. 5

    Measure the resistance of the compressor motor windings (e.g., U-V, V-W, W-U). Compare to specifications; unequal or open readings indicate internal motor fault.

  6. 6

    If external factors are ruled out and compressor windings are good, consider replacing the inverter P.C. board, as its current sensing or drive circuitry may be faulty.

Se alle koder i denne manualen (12)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Mitsubishi MSZ-FH06-18NA Heat Pump System