Er4
Mode designation error
Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
Hva betyr Er4 ?
This error occurs if parameter setting was attempted in External or NET operation mode while Pr.77 (Parameter write selection) is '1', or if parameter write was attempted when the command source is not the operation panel. It indicates a conflict between the current operating mode or command source and the attempt to write parameters.
Vanlige årsaker
- Invalid mode selection or transition attempted.
- Configuration error in mode selection parameters (e.g., P1-02).
- Attempting an unsupported operation for the current drive mode.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Switch the operation mode to 'PU operation mode' before attempting to make parameter settings.
- 2
If parameter write is desired regardless of operation mode, set Pr.77 to '2'.
- 3
If writing from the PU, ensure Pr.551 (PU mode operation command source selection) is set to '4'.
Verifisert teknisk data. Sist oppdatert: March 2026