Ethernet communication fault

Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive

Hva betyr EHR ?

This fault appears when Ethernet communication is interrupted by physical factors, especially when Pr.1431 (Ethernet signal loss detection function selection) is set to a value between '1' and '3'. It signifies a physical layer problem with the Ethernet connection to the inverter.

Vanlige årsaker

  • Disconnected or damaged Ethernet cable (RJ45 connector, internal conductors).
  • Network switch or router failure preventing data transmission.
  • Incorrect IP address, subnet mask, or gateway settings on the inverter (e.g., Pr.1408 to Pr.1413).
  • Excessive network traffic (broadcast storms) or collisions causing communication timeouts.
  • Physical damage to the inverter's Ethernet port or internal communication module.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the physical Ethernet cable connection at both the inverter and the network switch, ensuring the cable is securely latched.

  2. 2

    Check the link status LEDs on the inverter's Ethernet port and the connected network switch port (should be green/solid).

  3. 3

    Ping the inverter's IP address (set in Pr.1409) from a connected network device to verify basic network connectivity.

  4. 4

    Inspect the Ethernet cable for physical damage (kinks, cuts) and test its continuity using an Ethernet cable tester.

  5. 5

    Review Pr.1431 (Ethernet signal loss detection function selection) and associated timeout parameters to ensure they are appropriate for the network environment.

Se alle koder i denne manualen (55)