E.EHR

Ethernet Communication Fault

Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive

Hva betyr E.EHR ?

This fault indicates an interruption in Ethernet communication, often due to physical factors, when signal loss detection (Pr.1431 or Pr.1457 = '3') is enabled. The inverter output shuts off if communication is broken for the time set in Pr.1432. It can also occur in CC-Link IE Field Network Basic if data isn't received or the cyclic transmission status bit turns OFF, or in BACnet/IP if conflicting IP addresses are detected. A communication fault can stop critical processes and lead to loss of control over the inverter.

Vanlige årsaker

  • Damaged Ethernet cable (e.g., broken conductors, bent RJ45 pins, improper shielding).
  • Incorrect IP address (Pr.1401), subnet mask (Pr.1402), or gateway (Pr.1403) settings.
  • Network switch or router failure preventing communication to/from the inverter.
  • Loose connection at the inverter's RJ45 port or the network switch/PLC port.
  • Communication signal loss detection parameter (Pr.1431 or Pr.1457 = '3') configured with an excessively short timeout.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect Ethernet cable for physical damage; replace with a known good CAT5e/CAT6 cable if suspect.

  2. 2

    Verify IP address (Pr.1401), subnet mask (Pr.1402), and gateway (Pr.1403) settings are correct for the network configuration.

  3. 3

    Ensure the Ethernet cable is securely connected to the inverter's RJ45 port and the network switch or PLC.

  4. 4

    Ping the inverter's IP address from a connected device to confirm basic network connectivity.

  5. 5

    Check communication loss detection parameters (Pr.1431 or Pr.1457) and their timeout settings (e.g., Pr.1432) for appropriate values.