Oversetter...
U6

Compressor Overcurrent (Overload) Cut-off

Mitsubishi Electric · R410A Systems

Hva betyr U6 ?

The compressor has experienced an overcurrent condition due to an overload, leading to a safety cut-off. This could be caused by mechanical issues, excessively high head pressure, or an electrical fault within the compressor motor or associated circuit.

Vanlige årsaker

  • Compressor overcurrent due to overload.
  • Excessive mechanical load on the compressor.
  • Thermal overload protection of the compressor tripped.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure compressor running current on all three phases using a clamp meter — compare measured values to the motor nameplate FLA.

  2. 2

    Measure discharge and suction pressures to rule out high head pressure or liquid slugging as a cause.

  3. 3

    Measure winding resistance of the compressor motor phases (U-V, V-W, U-W) and to ground using an ohmmeter — expect balanced resistance and no ground fault.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Mitsubishi Electric R410A Systems