Abnormal High Discharging Temperature / Inner Thermostat (49C) Operation
Mitsubishi Electric · R410A Systems
Hva betyr U2 ?
The compressor discharge temperature is excessively high OR the internal thermostat (49C) on the outdoor unit has activated due to an over-temperature condition. Both indicate an overheating issue within the outdoor unit or its components, risking compressor damage.
Vanlige årsaker
- High discharge temperature detected.
- Operation of the inner thermostat (49C).
- Overheating condition in the discharge line.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure discharge pressure and temperature at the compressor outlet using appropriate gauges and probes.
- 2
Verify condenser coil cleanliness and ensure unrestricted airflow over the coil and around the compressor.
- 3
Check refrigerant charge using manifold gauges and subcooling/superheat calculations — ensure it's not overcharged.
- 4
Measure the temperature of the compressor casing using an infrared thermometer.
- 5
Verify the operation and rotation direction of the outdoor fan motor.