E45

Inverter to Outdoor PCB Transmission Error

Mitsubishi Electric · R410A Systems

Hva betyr E45 ?

A communication error has occurred between the inverter and the outdoor unit PCB, possibly due to a loose connection at the Cn1 terminal. This disrupts the control of the compressor by the inverter.

Vanlige årsaker

  • Communication failure between the inverter's main PCB and the outdoor unit's control PCB.
  • Loose or damaged communication wiring (e.g., terminal blocks P1-P5).
  • Faulty main PCB on either the inverter or outdoor unit.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect the Cn1 connector on both the outdoor unit PCB and the inverter board — verify it is securely seated.

  2. 2

    Check the continuity and integrity of the wiring connected to Cn1 using a multimeter.

  3. 3

    Verify stable power supply to both the inverter board and the outdoor unit PCB.