Oversetter...
E37
Outdoor Heat Exchanger Sensor (ThOR) Defective or Connection Issue
Mitsubishi Electric · R410A Systems
Hva betyr E37 ?
The outdoor unit's heat exchanger sensor (ThOR) is defective (open circuit) or has a poor connection to the outdoor unit PCB. This affects the system's ability to accurately monitor and control refrigerant temperatures within the outdoor coil.
Vanlige årsaker
- Outdoor heat exchanger temperature sensor (ThOR) malfunction.
- Electrical connection to the ThOR sensor is compromised.
- Sensor reading is outside the expected operational range.
- Defective sensor element.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure the resistance of the ThOR sensor at its leads — compare to a resistance-temperature chart if available.
- 2
Inspect the ThOR sensor's connector on the outdoor unit PCB — verify it is securely seated and free from corrosion.
- 3
Check for damage to the sensor wiring between the sensor and the PCB using a multimeter for continuity.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Mitsubishi Electric R410A Systems