MULTI CPU DOWN

Mitsubishi Electric · Q-series Programmable Controller

Hva betyr 7000 ?

This error code signifies a stop error originating from QCPU No. 1 in a multiple CPU system. When this occurs, other QCPUs/motion CPUs (No. 2 to 4) also experience a 'MULTI CPU DOWN' error, leading to the complete halt of the entire multiple CPU system. This fault indicates that the primary CPU has encountered a critical issue, preventing further execution across all involved CPUs.

Vanlige årsaker

  • A stop error has occurred at QCPU No. 1, which functions as the host CPU in the multiple CPU system.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Utilize the PLC diagnostics tool within GX Works2 to confirm the precise error cause for QCPU No. 1.

  2. 2

    Address and remove the identified error cause on QCPU No. 1.

  3. 3

    Reset QCPU No. 1 or cycle the power of the programmable controller; this action simultaneously resets and restores all QCPUs within the entire multiple CPU system.