1010
END Instruction Not Executed
Mitsubishi Electric · MELSEC System Q/L Series
Hva betyr 1010 ?
The entire program was executed without the proper execution of an END instruction. This issue can arise if the END instruction is misread due to electrical noise or if it has been inadvertently changed to another instruction code.
Vanlige årsaker
- Entire program executed without the execution of an END instruction.
- END instruction was read as another instruction code due to noise.
- The END instruction has been changed to another instruction code.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Implement noise reduction measures for the control system environment.
- 2
Reset the CPU module and attempt to RUN it again.
- 3
If the same error is displayed again after resetting, diagnose for a CPU module hardware fault.
Verifisert teknisk data. Sist oppdatert: March 2026