Oversetter...
F112

Faulty Loop Status / Mixed Network Modules

Mitsubishi Electric · MELSEC Q-series MELSECNET/H

Hva betyr F112 ?

The network loop is in a faulty state, indicating a serious communication problem. This can be caused by physical network issues or incompatible network module types being mixed within the same system.

Vanlige årsaker

  • Faulty network cables or incorrect cable wirings
  • Faulty network hardware
  • Electrical noise
  • Duplicate station numbers or duplicate control/remote master stations
  • Mixing of MESLECNET/H and MELSECNET/10 network modules in the same system

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect network cables for damage, integrity, and correct wiring

  2. 2

    Check for sources of electrical noise impacting communication

  3. 3

    Verify all station numbers are unique

  4. 4

    Confirm control station and remote master station settings are not duplicated

  5. 5

    Ensure that only one type of network module (e.g., MESLECNET/H or MELSECNET/10) is used within the same network, matching the control station type

  6. 6

    Check for faulty network hardware

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Mitsubishi Electric MELSEC Q-series MELSECNET/H