F108

Baton Pass Error (Baton Duplicated)

Mitsubishi Electric · MELSEC Q-series MELSECNET/H

Hva betyr F108 ?

A duplicate baton has been detected on the network, indicating a configuration error or physical fault that could lead to communication conflicts and instability. This typically arises from incorrect station numbering or control station settings.

Vanlige årsaker

  • Duplication of station numbers across the network
  • Duplication of control station settings
  • Faulty network cables, wire breakages, or faulty connector connections
  • Uninstalled or loose terminal resistors

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Execute the setup confirmation test (Section 4.8.2 or 3.8.2) to check for duplicate station numbers

  2. 2

    Execute the setup confirmation test (Section 4.8.2 or 3.8.2) to check for duplicate control station settings

  3. 3

    Inspect all network cables for physical damage, wire breakages, or faulty connector connections

  4. 4

    Verify that all terminating resistors are correctly installed and securely connected