Oversetter...
2401H

Module verification error

Mitsubishi Electric · MELSEC iQ-R Series

Hva betyr 2401H ?

The system detected an issue during module verification. This error indicates a discrepancy or problem during the module's verification process. If the "Direct change setting" is enabled, the system might continue operation without stopping, but the error itself will persist.

Vanlige årsaker

  • The "CPU Module Operation Setting at Error Detected Module Verify Error" parameter is set to "Stop".
  • A discrepancy occurred during module verification.
  • A module was physically removed or experienced a failure during operation while "Direct change setting" was enabled.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the "Direct change setting" parameter at [Parameter] -> Module model name -> [CPU Parameter] -> "RAS Setting" -> "Online module change setting".

  2. 2

    Check the "CPU Module Operation Setting at Error Detected Module Verify Error" setting.

  3. 3

    If the error remains and affects the system with "Direct change setting" enabled, set it to "Disable" and perform an online module change using special relays and special registers.

Se alle koder i denne manualen (9)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Mitsubishi Electric MELSEC iQ-R Series
Mitsubishi Electric 2401H support: Module verification erro… | ErrorLib