Oversetter...
Undervoltage

Undervoltage

Mitsubishi Electric · FR-D700 Inverter

Hva betyr Undervoltage ?

The voltage at the main circuit power supply has dropped below an acceptable operating level. This can be caused by issues in the incoming power supply line, insufficient capacity, or a fault within the power supply itself, leading to insufficient power for the inverter and potential damage if the voltage fluctuates excessively. The inverter output is shut off.

Vanlige årsaker

  • Sag or complete loss of one or more phases in the incoming AC main power supply (e.g., R/L1, S/L2, T/L3 terminals).
  • Insufficient power supply capacity for the driven load, causing voltage drops during peak current demand.
  • Loose or corroded connections in the main power circuit, leading to voltage drop under load.
  • Faulty main circuit capacitors within the inverter, affecting DC bus voltage regulation.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the incoming AC line voltage at the inverter's main input terminals (R/L1, S/L2, T/L3) using a multimeter or power quality analyzer.

  2. 2

    Check for loose connections or corrosion on the main power wiring terminals, both at the inverter and upstream circuit breakers/contactors.

  3. 3

    Verify the capacity of the upstream transformer and circuit breaker to ensure they can adequately supply the inverter and motor.

  4. 4

    Monitor the DC bus voltage (e.g., using Pr. 08 "DC Bus Voltage" monitor function) during operation to observe sag trends.

  5. 5

    Consult an electrician to inspect the facility's power distribution system for sags or imbalances affecting the inverter's supply.

Se alle koder i denne manualen (78)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Mitsubishi Electric FR-D700 Inverter