E.OPT

Option alarm

Mitsubishi Electric · A500 Inverter

Hva betyr E.OPT ?

This alarm stops the inverter output if two or more communication options are fitted (with exceptions for FR-A5NR). If a high power factor converter is connected, this alarm appears if an AC power supply is accidentally connected to the R, S, T <L1, L2, L3> terminals, which can result in inverter damage.

Vanlige årsaker

  • An alarm condition has been triggered by an optional accessory or expansion module.
  • Communication failure with a connected option device.
  • Option device internal fault.
  • Incorrect configuration of the option device within the system.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify that only one communication option (excluding FR-A5NR if used solely for relay output) is installed in the inverter.

  2. 2

    If a high power factor converter is connected, confirm that no AC power supply is connected to the R, S, T <L1, L2, L3> terminals.

  3. 3

    Check the setting of parameter Pr. 30.

  4. 4

    Verify the wiring for high power factor converter connections.