x250

2.Flash Err

Lenze · 9300 Series

Hva betyr x250 ?

An error occurred during access to the FLASH memory, indicating the PLC program attempted to access non-available or defective memory. This could signify a hardware issue with the FLASH memory module, preventing proper program execution or data storage.

Vanlige årsaker

  • Degradation or physical damage to specific sectors of the controller's FLASH memory module, making them unreadable or unwritable.
  • Power supply instability (e.g., `24VDC_Input_Voltage` fluctuating below 21V) or electrical noise during FLASH read/write operations, corrupting data.
  • Firmware bug attempting to access an invalid memory address outside the allocated FLASH region, causing an access violation.
  • Exceeded write endurance limits of a particular FLASH memory block, leading to wear-out failures over time.
  • Electromagnetic interference (EMI) disrupting FLASH memory access during critical operations, causing read/write errors.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Attempt to re-download the PLC program and all associated data (e.g., parameters, recipes) to the controller to overwrite potentially corrupted FLASH sectors.

  2. 2

    2. Perform a comprehensive memory test or diagnostic routine on the controller's FLASH memory, if available through the engineering tool's diagnostics menu.

  3. 3

    3. Verify the stability of the controller's power supply (e.g., `Power_Supply_Output_Voltage` measured at terminals `L+` and `M`) and check for transient voltage drops.

  4. 4

    4. If the error persists after re-download and power verification, consider replacing the controller or the FLASH memory module (if it is a modular component).

  5. 5

    5. Ensure proper grounding and shielding of the control cabinet and internal wiring to minimize EMI effects on sensitive memory components.

Se alle koder i denne manualen (145)