H10 Thermal sensor error at heatsink

Lenze · 9300 Series

Hva betyr x110 ?

An error has been detected with the thermal sensor responsible for monitoring the heatsink temperature. This indicates a fault with the sensor itself or its wiring, compromising the heatsink temperature monitoring. This monitoring is controlled by parameter C0588.

Vanlige årsaker

  • Broken wire or loose connection to the heatsink thermal sensor (e.g., internal PTC or NTC).
  • Internal heatsink temperature sensor failure, reporting an out-of-range value (e.g., open circuit or short circuit).
  • Dust accumulation or obstruction around the heatsink, leading to localized overheating and sensor activation.
  • Fan failure preventing proper airflow over the heatsink, causing actual high temperature and sensor trip.
  • Faulty main control board input for the heatsink temperature sensor.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Power down the drive, wait for capacitor discharge, then inspect the heatsink for excessive dust buildup and clean if necessary.

  2. 2

    Verify the operation of any cooling fans by observing them during startup or checking their auxiliary power supply.

  3. 3

    Measure the resistance of the heatsink temperature sensor terminals (if accessible) and compare to expected values for the sensor type (e.g., NTC).

  4. 4

    Inspect the internal wiring from the heatsink sensor to the main control board for any breaks or disconnections.

  5. 5

    If the fault persists and external factors are ruled out, internal sensor or control board failure is likely, requiring service.