EEr External monitoring (activated via DCTRL)
Lenze · 9300 Series
Hva betyr x091 ?
An external monitoring function has triggered this fault, which is activated via DCTRL (Drive Control) and configured through parameter C0581. The 'x' in the code indicates the response type: 0 for TRIP, 1 for message, 2 for warning.
Vanlige årsaker
- The external safety circuit (e.g., E-Stop, light curtain, guard door switch) connected to a digital input configured for external monitoring has opened.
- A signal on a digital input configured as an external fault input via parameter C0581 has changed state, triggering the fault.
- Wiring fault (e.g., broken wire, short circuit) in the external monitoring circuit connected to the drive.
- External PLC or control system outputting an incorrect signal to the drive's external monitoring input.
- Incorrect configuration of parameter C0581, where a normally closed contact is expected but an open contact is provided.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Identify the specific digital input assigned as the external monitoring input via parameter C0581 and measure its voltage state.
- 2
Trace the wiring from the identified digital input to the external monitoring device (e.g., E-stop button, safety relay contact).
- 3
Verify the status of all external safety devices and ensure their contacts are closed (or open, as configured) as expected.
- 4
Check the logic configured in parameter C0581 (e.g., active high or active low) and ensure it matches the external signal.
- 5
Perform a continuity test on the external monitoring circuit wiring to identify any breaks or short circuits.