Oversetter...
x085

Sd5 Analog input current < 2 mA

Lenze · 9300 Series

Hva betyr x085 ?

The input current at analog input X6/1 or X6/2 has fallen below 2 mA. This monitoring function is only active if parameter C0034 is set to 1, indicating a low current condition on the analog input.

Vanlige årsaker

  • Broken wire or loose connection in the 4-20mA current loop connected to analog input X6/1 or X6/2.
  • Faulty 4-20mA current loop sensor (e.g., pressure transducer, flow meter) failing to output the minimum 4mA signal.
  • External power supply for the current loop failing or dropping below the required voltage for the sensor.
  • Excessive resistance in the current loop wiring, causing a voltage drop that prevents sufficient current flow.
  • Incorrect configuration of parameter C0034, which enables the < 2mA monitoring function.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the current directly in series with the analog input X6/1 or X6/2 using an ammeter to verify the current value.

  2. 2

    Inspect all wiring connections for the 4-20mA loop, ensuring secure terminals and checking for cable damage or splices.

  3. 3

    Verify the external power supply for the current loop sensor, ensuring it provides the correct voltage (e.g., 24VDC) and adequate current capacity.

  4. 4

    Test the 4-20mA sensor independently by applying its rated power and measuring its output current with an ammeter.

  5. 5

    Check parameter C0034; if the monitoring is not desired or needed, consider changing its setting (e.g., to 0 to disable low current fault).

Se alle koder i denne manualen (145)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder