x054

OH4 Heatsink temperature > C0122

Lenze · 9300 Series

Hva betyr x054 ?

The heatsink temperature has exceeded the specific threshold value set in parameter C0122. This is an advance warning for heatsink overheating, which can be caused by high ambient temperatures (Tu > +40°C or +50°C), a dirty heatsink, or an incorrect mounting position. This monitoring can be switched off via C0582.

Vanlige årsaker

  • Control cabinet ambient temperature (Tu) is high, pushing the drive's heatsink temperature close to the warning threshold set in C0122.
  • Partial blockage of heatsink fins with dust or debris, slightly reducing cooling efficiency without completely stopping airflow.
  • Drive cooling fan operating at reduced speed or intermittently, not providing optimal airflow.
  • Drive operating continuously near its maximum rated current, generating more heat than usual.
  • Parameter C0122 (Heatsink temperature warning threshold) is set too aggressively (too low) for the application's operating conditions.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the control cabinet ambient temperature (e.g., with a thermometer) and compare it to the drive's specification.

  2. 2

    Clean the drive's heatsink fins with compressed air to ensure maximum surface area for heat dissipation.

  3. 3

    Monitor the drive's internal cooling fan operation, checking for consistent rotation and lack of obstruction.

  4. 4

    Review parameter C0122 (Heatsink temperature warning threshold) and consider raising it slightly if current operating conditions are normal.

  5. 5

    Ensure adequate ventilation in the control cabinet, checking fan filters and ensuring sufficient clearance around the drive for airflow.

Se alle koder i denne manualen (145)
Verifisert teknisk data. Sist oppdatert: March 2026