Error during rotor position adjustment

Lenze · 9300 Series

Hva betyr PL ?

The rotor position adjustment process was cancelled, often because an Sd7 or Sd8 error occurred during adjustment with an absolute value encoder. Without a successfully executed rotor position adjustment, the drive may carry out uncontrolled movements.

Vanlige årsaker

  • Incorrect motor data entered into parameters (e.g., C0203, C0204, C0205) preventing accurate motor model computation during adjustment.
  • Absolute encoder feedback cable wiring fault (e.g., loose shield, swapped A/B/Z signals) causing corrupted position data during the adjustment routine.
  • Mechanical coupling issues (e.g., backlash, slippage) between the motor shaft and the encoder, leading to inconsistent position feedback.
  • External mechanical load applied to the motor during the rotor position adjustment procedure, preventing free rotation or causing unexpected torque.
  • Motor brake failing to release completely during the adjustment process, impeding motor rotation.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify motor nameplate data and cross-check against parameters C0203 (Rated current), C0204 (Rated voltage), C0205 (Rated speed), and C0206 (Rated frequency) for accuracy.

  2. 2

    Inspect the absolute encoder cable for insulation damage, proper shielding connection to the drive's PE terminal, and continuity between the encoder and drive terminals (e.g., X11.1, X11.2, X11.3).

  3. 3

    Mechanically decouple the motor from the load if possible, then re-attempt the rotor position adjustment procedure (Parameter P0-23 = 1).

  4. 4

    Check for any external forces or obstructions preventing free rotation of the motor shaft during the adjustment process.

  5. 5

    If a motor brake is present, measure the voltage at the brake terminals (e.g., X1.3, X1.4) to confirm it is releasing correctly when energized (24VDC).

Se alle koder i denne manualen (145)