Oversetter...
077

PR3

Lenze · 9300 Series

Hva betyr 077 ?

A checksum error was detected in parameter set 3 during loading or transfer via the keypad. This indicates a fault in the parameter data or incompatibility with the loaded software version. The Lenze default settings are loaded automatically.

Vanlige årsaker

  • Corrupted parameter data: The parameter data being loaded (e.g., from a keypad, memory module, or communication interface) for parameter set 3 is corrupted during transmission or storage.
  • Incompatible firmware/software: The parameter set 3 saved in the keypad or external memory was created with a different firmware version of the device, leading to data structure mismatch.
  • Keypad malfunction: The keypad itself has an internal fault, causing incorrect data to be written or read for parameter set 3, resulting in a checksum mismatch.
  • Power interruption during write: Power supply fluctuation or interruption occurred precisely while parameter set 3 was being written to non-volatile memory.
  • Internal memory corruption: A rare internal fault in the device's non-volatile memory (e.g., EEPROM or Flash) where parameter set 3 is stored.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Re-attempt to load parameter set 3, ensuring a stable power supply and observing for any communication errors during the process.

  2. 2

    Try loading the factory default parameter set (e.g., using parameter P0-10 = 100) and then manually re-enter critical parameters for set 3 to confirm data storage integrity.

  3. 3

    If loading from an external keypad or module, try using a different, known-good keypad/module to eliminate the possibility of a hardware fault.

  4. 4

    If available, upgrade the device firmware to the latest compatible version (refer to manufacturer's documentation) and then try loading parameter set 3 again.

  5. 5

    Backup existing parameters (if possible) and perform a full device reset (e.g., P0-10 = 110 for complete factory reset) before attempting to reload parameter set 3.

Se alle koder i denne manualen (145)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder