Oversetter...
066

CE5

Lenze · 9300 Series

Hva betyr 066 ?

A time-out has occurred on the system bus (CAN) during remote parameterization (C0370, C0371), indicating a communication error of the gateway function. The slave device did not respond within the communication monitoring time.

Vanlige årsaker

  • Slave device unpowered or offline: The targeted slave device is not powered on, is in a fault state, or has physically disconnected from the CAN bus.
  • Incorrect slave address: The CAN bus address (e.g., parameter P7-02 for slave ID) used in the remote parameterization command (C0370, C0371) does not match any active device on the bus.
  • Gateway configuration error: The gateway function within the master device (e.g., parameter P7-05 for gateway timeout) is misconfigured or has an internal fault preventing proper message forwarding.
  • High bus load/latency: Excessive data traffic on the CAN bus is causing significant delays, leading to the parameterization command timing out before a response can be received.
  • Inconsistent firmware: Firmware versions between the master and slave devices are incompatible for remote parameterization functions.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify that the slave device targeted by remote parameterization (e.g., based on slave ID set by P7-02) is powered on and not in a fault state (e.g., check its status LEDs).

  2. 2

    Confirm the CAN bus address of the slave device (e.g., physically set by DIP switches or configured via parameter P7-02) matches the address used in the remote command (C0370, C0371).

  3. 3

    Monitor the CAN bus traffic using a CAN analyzer to check for excessive load or intermittent communication errors during parameterization attempts.

  4. 4

    Temporarily increase the communication timeout parameter (e.g., P7-05) on the master device to see if the issue is solely due to latency, then re-evaluate.

  5. 5

    Check the device manual for specific parameterization registers (C0370, C0371) and their expected response times; ensure no conflicting bus communication is active.

Se alle koder i denne manualen (145)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder