Oversetter...
0210

float Cycl.-T

Lenze · 9300 Series

Hva betyr 0210 ?

A float error, such as division by zero, has occurred in the cyclic task (PLC_PRG ID 1) during real number calculations. This indicates an issue within the PLC program's arithmetic operations that impacts the cyclic execution.

Vanlige årsaker

  • Division by zero within the `PLC_PRG` cyclic task, typically from user-defined calculations involving process variables (e.g., `MOTOR_SPEED / LOAD_FACTOR`).
  • Floating-point overflow or underflow occurring in complex mathematical functions (e.g., PID calculations, scaling functions) within the `PLC_PRG`.
  • Uninitialized or corrupted real-type variables used in arithmetic operations, leading to unpredictable `NAN` (Not A Number) results.
  • Input sensor values (e.g., analog inputs on `AI_Channel_1`) converted to `REAL` falling outside expected ranges, causing invalid mathematical operations.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Connect to the controller with the programming environment and use the debugger to pinpoint the exact line of code within `PLC_PRG` causing the float error.

  2. 2

    2. Add conditional logic to all division operations in `PLC_PRG` to prevent division by zero (e.g., `IF Denominator <> 0.0 THEN Output := Numerator / Denominator; END_IF;`).

  3. 3

    3. Validate all real-type input variables from analog modules (e.g., `AI_01_Value`) using `LIMIT` or range checks before they are used in calculations.

  4. 4

    4. Initialize all `REAL` variables at declaration or upon program start to a known valid value (e.g., `0.0`) to avoid using uninitialized data.

  5. 5

    5. Monitor CPU load and memory usage (e.g., using `Task Info` view in the programming tool) for the cyclic task to detect potential resource contention affecting calculations.

Se alle koder i denne manualen (145)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder