Oversetter...
0078

PR4 (Checksum error in parameter set 4)

Lenze · 9300 Series

Hva betyr 0078 ?

A checksum error has been detected in parameter set 4, indicating a fault during loading or an interruption during transfer via the keypad. This can also occur if saved parameters are incompatible with the loaded software version.

Vanlige årsaker

  • Interruption of parameter transfer (e.g., during upload from keypad or communication bus) to parameter set 4.
  • Data corruption in the non-volatile memory bank corresponding to parameter set 4.
  • Attempting to load a parameter set 4 that was created on an older or incompatible firmware version.
  • Power loss or voltage fluctuation during the save operation for parameter set 4.
  • Faulty keypad or communication interface transmitting incorrect data for parameter set 4.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Cycle power to the drive and attempt to reload parameter set 4 from a known good backup file using the appropriate software tool.

  2. 2

    Verify the integrity of the parameter set 4 file used for transfer and ensure it matches the current firmware version (C0004).

  3. 3

    If transferring via keypad, ensure a stable connection and retry the transfer of parameter set 4, monitoring for interruptions.

  4. 4

    Set C0003 to 1 (factory default) to clear any corrupted settings, then carefully reconfigure only the necessary parameters in set 4.

  5. 5

    Check the drive's communication bus (e.g., CAN, EtherCAT) for noise or intermittent connections if parameter set 4 transfer occurs over the bus.

Se alle koder i denne manualen (145)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder