0071

CCr (System failure)

Lenze · 9300 Series

Hva betyr 0071 ?

A system failure has occurred, likely due to strong interference injection on control cables or ground/earth loops in the wiring. This indicates an electrical noise or grounding issue affecting the controller's stability.

Vanlige årsaker

  • Electromagnetic interference (EMI) ingress through control cables routed too close to power cables or unshielded.
  • Ground loop currents flowing through control circuit ground connections due to multiple grounding points at different potentials.
  • Insufficient or faulty common mode filtering on the drive's control power supply.
  • Internal hardware fault within the drive's control board due to power fluctuations or component degradation.
  • Inadequate grounding of the drive chassis or the control cabinet, leading to poor noise dissipation.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Power down the drive, re-route control cables away from power cables (minimum 10cm separation) and ensure shielding is properly terminated at one end to chassis ground.

  2. 2

    2. Verify all grounding connections for the drive and control system are robust and follow a single-point grounding scheme if possible.

  3. 3

    3. Check the incoming control voltage at the drive's control power terminals for stability using a multimeter, looking for sags or spikes.

  4. 4

    4. Measure the resistance between the drive chassis and the main control cabinet ground to ensure a low impedance path (ideally < 0.1 Ohm).

  5. 5

    5. Isolate external control signals by temporarily disconnecting them one by one to identify a potential source of interference.