STA1 (PMB_SR) Flashing

PMB_SR Microcontroller Internal Fault

Kuka · Sunrise Cabinet Med Controller

Hva betyr STA1 (PMB_SR) Flashing ?

The STA1 (PMB_SR) μC USB LED is flashing at a rate other than 1 Hz (normal) or 10 Hz (boot phase), indicating an internal fault within the PMB_SR microcontroller. This suggests the microcontroller is not operating correctly, possibly due to a core component malfunction or a corrupt firmware state. The fault might be related to the power supply to the module or internal processing errors.

Vanlige årsaker

  • The PMB_SR microcontroller has encountered an internal processing error, indicated by flashing status.
  • Internal fault within the power module board microcontroller.
  • The PMB_SR module's internal software or hardware has failed.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the infeed power supply at connector X1.

  2. 2

    Verify the status of the PWR/5V LED. If the PWR/5V LED lights up, exchange the CCU_SR module, as the internal fault persists despite power being present.

  3. 3

    If the PWR/5V LED is not lit, troubleshoot the 5V power supply before considering CCU_SR module replacement.