Oversetter...
PWR/1.2V Off (CIB_SR)
CIB_SR 1.2V Power Supply Not Present
Kuka · Sunrise Cabinet Med Controller
Hva betyr PWR/1.2V Off (CIB_SR) ?
The PWR/1.2V Green LED for the CIB_SR module is OFF, indicating a lack of 1.2V supply voltage to the module. This absence of critical operating voltage prevents the CIB_SR module from functioning correctly and could result in the non-operation of interconnected I/O nodes.
Vanlige årsaker
- The 1.2V power supply to the CIB_SR module is not present.
- The CIB_SR module requires 1.2V power, which is currently absent.
- Failure or absence of the 1.2V power rail for the CIB_SR communication board.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check fuse F17.3 on the CCU_SR for continuity and proper rating.
- 2
Verify the presence and correct seating of jumper plug X308.
- 3
Check fuse F308 on the CCU_SR for continuity and proper rating.
- 4
If an external supply is used via X308, check the external power supply to ensure it provides the rated voltage of 24 V.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Kuka Sunrise Cabinet Med Controller