Device temperature too high, KPP/KSP (axis)
Kuka · KR C4 Operating Instructions
Hva betyr 26111 ?
An overtemperature condition has been detected within the KPP or KSP device for a specific axis. This indicates that the internal operating temperature of the drive or control unit has exceeded its safe limits, potentially due to insufficient cooling or excessive load. Continued operation in this state can lead to component damage or premature failure.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the operational status of the cabinet cooling fan.
- 2
Measure the ambient temperature at the installation site of the equipment.
- 3
Review the program load to determine if it is excessively high for the axis, which can generate surplus heat.
- 4
Inspect the cooling circuit for any dirt accumulation and clean as necessary to ensure proper airflow.
- 5
Verify the operational status of the PC fan within the control system.
- 6
Perform a Power Off / Power On cycle of the entire system to reinitialize the drive bus.