Oversetter...
26047

Power supply failure, KPP/KSP (axis)

Kuka · KR C4 Operating Instructions

Hva betyr 26047 ?

The supply voltage for the KPP/KSP device has fallen below 300 V. This indicates an undervoltage condition on the power supply to the drive, which can prevent proper operation or lead to protective shutdown.

Vanlige årsaker

  • The internal power supply unit of the KPP/KSP drive has failed.
  • External DC power supply required by the KPP/KSP is out of range.
  • Voltage regulator failure within the KPP/KSP.
  • Short circuit on the KPP/KSP internal power rails.
  • Overload condition on the KPP/KSP power output.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the power lead connected to the KPP for disconnections or physical damage.

  2. 2

    Inspect the KPP cabling for loose or damaged connections, ensuring secure contacts.

  3. 3

    Reinitialize the drive bus by performing a Power Off / Power On cycle of the entire system.

  4. 4

    Check the KPP module itself for internal faults if input voltage is verified correct.

Se alle koder i denne manualen (22)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Kuka KR C4 Operating Instructions