Oversetter...
18
Over-speed Protection in Reversed Direction
Kone · Frequency Inverter
Hva betyr 18 ?
This error indicates that the motor speed has exceeded a safe limit while traveling in the reverse direction of the intended 'riding' or forward direction. This is a critical safety fault, often triggered by unintended reverse motion or a severe control issue.
Vanlige årsaker
- Unintended reverse rotation of the motor despite a forward command or no command.
- Loss of speed control by the drive leading to uncontrolled reverse motion.
- Incorrect over-speed protection threshold setting for reverse direction in drive parameters.
- Malfunctioning speed feedback device providing incorrect direction information.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify that no reverse run command signals are active if forward motion is expected.
- 2
Check for external forces or mechanical conditions that could be causing unintended reverse rotation of the motor.
- 3
Review and adjust the over-speed protection threshold parameter for the reverse direction in the drive's settings.
- 4
Inspect the speed feedback device (encoder) for proper operation and correct direction sensing.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Kone Frequency Inverter