Invalid addressing actual value data container A
Indramat · IndraDrive MPx02
Hva betyr E4009 ?
An error occurred during the index check in the multiplex channel of the IndraDrive MPx02. During cyclic data exchange, the index used to access "Data container A: configuration list actual value-x" points to a non-initialized position in the list, leading to issues with reading actual values.
Vanlige årsaker
- Incorrect configuration of "Data container A: configuration list actual value-x"; the list may not be properly sized or initialized.
- An invalid index or address in the high byte of S-0-0368 (Data container A: addressing) is attempting to access uninitialized memory.
- Corruption of data container A's configuration list for actual values.
- Logic error in the master controller or internal drive program attempting to read from an invalid address.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the configuration settings for "Data container A: configuration list actual value-x" in the IndraDrive MPx02 to ensure it is properly initialized and contains valid data.
- 2
Verify the high byte of parameter S-0-0368 (Data container A: addressing) to ensure it is pointing to a valid, initialized position within the data container.
- 3
Review the application logic that reads from "Data container A" via the multiplex channel for any out-of-bounds addressing attempts.
- 4
Consult the functional description of the firmware for "Multiplex Channel" for detailed information on proper configuration and addressing of data containers.
- 5
Perform a drive reset and re-download the configuration if data corruption is suspected.