Time interval of forced dynamization exceeded
Indramat · IndraDrive MPx02
Hva betyr E3110 ?
The IndraDrive MPx02 has detected that the starting lockout has not been activated within the specified time interval defined by parameter P-0-0103 (Time interval of forced dynamization). This indicates a potential safety-related issue if the lockout is not engaged as required, possibly allowing unintended startup.
Vanlige årsaker
- The configured time interval in P-0-0103 is too short or does not match the application's operational requirements.
- The starting lockout was not activated (e.g., by the safety logic or drive controller) within the allotted time.
- A delay in the external control system's logic preventing timely activation of the lockout.
- Incorrect parameter P-0-0103 setting preventing proper system response.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify the setting of parameter P-0-0103 (Time interval of forced dynamization) and ensure it is appropriate for the application's operating cycle and safety requirements.
- 2
Confirm that the control logic (PLC or master controller) is correctly activating the starting lockout within the specified time interval.
- 3
Review the sequence of operations for activating starting lockout to ensure it is performed in the correct order and timing.
- 4
If the interval is too short for the application's process, adjust P-0-0103 to a value that allows sufficient time for the starting lockout to be activated.