E2818

Phase failure

Indramat · IndraDrive MPx02

Hva betyr E2818 ?

The IndraDrive MPx02 has detected the loss of one or more phases of the incoming three-phase AC mains supply. This condition prevents proper operation, leading to unbalanced currents and insufficient power, and can damage the drive and motor if not addressed promptly.

Vanlige årsaker

  • Blown fuse or tripped circuit breaker in one phase of the incoming supply line.
  • Open circuit or loose connection in one of the mains power lines to the drive.
  • Fault in the upstream power transformer or distribution equipment.
  • Power utility issue leading to a single or multi-phase loss.
  • Incorrect wiring of the mains power supply.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Immediately power down the drive and visually inspect all fuses and circuit breakers in the incoming power supply circuit for the IndraDrive MPx02. Replace or reset as necessary.

  2. 2

    Measure the voltage between all three phases (L1-L2, L2-L3, L3-L1) at the input terminals of the drive to confirm the presence of all phases and balanced voltages.

  3. 3

    Check all power cable connections from the main supply to the drive, ensuring they are tight, correctly terminated, and free from corrosion.

  4. 4

    Investigate the upstream power distribution system, including contactors and transformers, for any component failures.

  5. 5

    If the problem persists and upstream power is confirmed healthy, the drive's input rectifier or phase sensing circuit may be faulty.

Se alle koder i denne manualen (56)