2062

Low Insulation Resistance

Huawei · SUN2000 Solar Inverter

Hva betyr 2062 ?

PV arrays are short-circuited with PE, or the ambient air around the PV array is damp, leading to poor insulation between the PV array and the ground. This presents a safety risk and can hinder inverter operation.

Vanlige årsaker

  • PV arrays are short-circuited with PE.
  • The ambient air of the PV array is damp and the insulation between the PV array and the ground is poor.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the output resistance of the PV array to ground. If there is a short circuit or lack of insulation, rectify it.

  2. 2

    Check that the PE cable of the SUN2000 is correctly connected.

  3. 3

    If you are sure that the impedance is less than the default value in a cloudy or rainy environment, log in to the mobile phone app, SmartLogger, or NMS and reset the insulation impedance protection threshold.