Low Array Insulation Resistance
Huawei · SUN2000 8-28KTL Solar Inverter
Hva betyr 313 ?
A major fault where the insulation resistance of the PV strings against ground is low, potentially due to a short circuit between strings and ground or installation in a permanently moist environment. This poses a safety risk and can lead to inverter shutdown.
Vanlige årsaker
- A short circuit between PV strings and the ground.
- The PV strings are installed in a permanently moist environment.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the insulation resistance against the ground of the PV strings.
- 2
If a short circuit is detected, rectify the fault.
- 3
If the insulation resistance against the ground is less than the default value in a rainy environment, set the ISO value (refer to 7.2.9 Setting Protection Parameters).