Frequency Abnormal
Huawei · SUN2000 8-28KTL Solar Inverter
Hva betyr 305 ?
A major fault indicating that the actual frequency of the connected power grid is outside the required range for the local grid. This can prevent the SUN2000 from synchronizing and feeding power, leading to shutdown.
Vanlige årsaker
- The actual frequency of the grid is higher than or lower than the required value for the local grid.
- An accidental grid abnormality.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Observe if the SUN2000 automatically reverts to normal operating status if the alarm occurred accidentally due to a temporary grid abnormality.
- 2
If the alarm occurs repeatedly, check if the grid frequency is within the allowed range.
- 3
If the grid frequency is within the allowed range but alarms persist, change the grid overfrequency and underfrequency protection points after obtaining approval from the local power operator (refer to 7.2.9 Setting Protection Parameters).