231-E006

CC%2 input (NE2) not equal to 0

Heidenhain · TNC CNC Controllers

Hva betyr 231-E006 ?

This error signifies a problem during the dynamic test of the second emergency-stop loop in the Heidenhain TNC CNC Controller. During this safety test, a 0V signal is expected at input NE2 within 1.5 minutes. If a 24V signal remains present, it indicates a failure in the emergency-stop circuit, compromising the machine's safety function.

Vanlige årsaker

  • Incorrect or damaged wiring connecting to input NE2 or within the second emergency-stop loop.
  • A malfunctioning emergency-stop button that fails to open its contacts, thus preventing the signal at NE2 from dropping to 0V.
  • Internal hardware defect within the safety monitoring module or the input circuitry associated with NE2.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the wiring of input NE2 and the entire second emergency-stop loop for continuity, proper terminations, and any signs of damage or short circuits.

  2. 2

    Inspect all emergency-stop buttons connected to the second loop for mechanical damage, correct operation, and ensure their contacts transition correctly (normally closed) when activated.

  3. 3

    Measure the voltage at input NE2 during the dynamic test sequence; confirm that it transitions to 0V as expected within the 1.5-minute timeout.

  4. 4

    If wiring and emergency-stop buttons are confirmed functional, consult a Heidenhain service agency for further diagnostics on potential hardware defects in the safety monitoring module.