Insulation Error
Fronius · Symo Advanced
Hva betyr 204 ?
This status code indicates that the insulation resistance of the solar module strings connected to the Fronius Primo GEN24 208-240 inverter is too low. This is a critical safety issue, often caused by moisture ingress or physical damage to the solar modules or DC cabling, compromising electrical isolation.
Vanlige årsaker
- Moisture ingress into the solar modules or their junction boxes.
- Damage to the insulation of the solar modules, such as cracks or delamination.
- Damage to the insulation of the DC cabling (PV+ or PV-) due to mechanical stress, UV degradation, or animal damage.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure the insulation resistance of the solar module strings between PV+ to ground (GND) and PV- to ground (GND) using a megohmmeter (e.g., at 500VDC). Expect values >1 MΩ.
- 2
Inspect all DC cabling for visible signs of damage, cuts, abrasions, or signs of moisture ingress.
- 3
Examine solar modules for physical damage to the backsheet, frame, or glass that could compromise insulation.
- 4
De-energize the inverter (switch off AC and DC disconnects), wait for 5 minutes, then re-energize to reset. If the message persists, the inverter may require service.