No AC grid
Fronius · Primo GEN24 Operating Instructions
Hva betyr 107 ?
This code indicates a complete absence of an AC grid connection, preventing the inverter from feeding energy. The inverter will automatically attempt to connect again once an AC grid is detected.
Vanlige årsaker
- Loss of AC power from the public grid.
- Open circuit breaker or faulty connection on the AC side of the inverter.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the AC voltage on the inverter connection sockets; it must be 220/230 V (+10% / -5%) or 380/400 V (+10% / -5%).
- 2
Verify that all AC circuit breakers leading to the inverter are closed and functional.
- 3
Inspect all AC cable connections for integrity and secure termination.
Verifisert teknisk data. Sist oppdatert: March 2026