Inverter DC Link Undervoltage

Fanuc · Series 30i/31i/32i-MODEL B Plus

Hva betyr 5 ?

This alarm indicates an undervoltage condition in the DC link of the Inverter (Servo Amplifier). This can stem from loose DC link connections or issues with the control printed-circuit board's seating. If multiple modules are affected, the Power Supply may be the root cause.

Vanlige årsaker

  • Loose screws for the DC link connection cable (bar).
  • DC link low voltage condition occurring in more than one module (potentially Power Supply related).
  • Faceplate (control printed-circuit board) of the Servo Amplifier not fully seated.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check that the screws for the DC link connection cable (bar) are tight.

  2. 2

    If the alarm occurs in only one Servo Amplifier, ensure the faceplate (control printed-circuit board) of that Servo Amplifier is pushed in as far as it will go.

  3. 3

    Replace the Servo Amplifier in which this alarm has occurred.

Se alle koder i denne manualen (38)
Verifisert teknisk data. Sist oppdatert: March 2026